What we measure
The instruments behind every reading.
Each reading on IoTyX starts with an instrument in the field, read by an Ilonnati controller. These are the typical instruments for each reading, with their ranges; the model is chosen for each site.
- Instruments
- 11 types
- Connections
- RS-485 Modbus, 4–20 mA, pulse, wireless
- Read by
- An Ilonnati controller on site
Where they are fitted
- Elevated reservoir
- Pump set
- Motorised valve
- Meter at each connection
- Ilonnati controller
Water quantity
How much water moves, from the source to the connection: the figure every loss calculation starts from.
2 instruments
Electromagnetic flow meter
Measures flow in a full pipe with no moving parts, for bulk metering at a source, a zone inlet or a plant.
- Pipe sizes
- 3 to 3,000 mm
- Velocity
- 0.1 to 15 m/s, 1 mm/s resolution
- Accuracy
- ±0.3% of reading above 1 m/s (25–600 mm pipes)
- Outputs
- 4–20 mA, pulse, frequency, RS-485 Modbus
- Power
- 220 V AC or 24 V DC
- Forward, reverse and net totals
- Alarms for an empty pipe, and for high and low flow
- Outputs isolated from the line
Fitted at Source and zone inlets, treatment works, plant process lines
Mechanical water meter with a pulse sensor
A Class B bulk meter whose dial is read by a clip-on pulse sensor, so an existing meter can report without being replaced.
- Sizes
- 40 to 500 mm
- Permanent flow
- 15 m³/h at 40 mm to 1,500 m³/h at 500 mm
- Accuracy
- ±3% low-flow zone, ±1.5% upper zone
- Pulse
- One per 10, 100 or 1,000 litres, by size
- Pressure
- Up to 10 bar
- Mechanism lifts out for service; the meter stays in the pipe
- Dry, sealed dial, not affected by external magnets
- Needs 10 pipe diameters of straight pipe before it and 5 after
Fitted at Connections, bulk supply points, campuses and housing
Level and pressure
How full each tank is, and whether each zone of a network is being supplied.
2 instruments
Pressure transmitter
Reports the pressure in a main, so low pressure, a burst or an unserved zone shows at once.
- Range
- 0–6 or 0–10 bar
- Accuracy
- 0.5%
- Output
- 4–20 mA
- Build
- IP65, 316L stainless steel
- Supply
- 12 or 24 V DC
- Read by the controller through an analog input
- Works from −20 to 80 °C
Fitted at Mains, zone boundaries, pump delivery lines
Radar level sensor
Measures the level of a tank, sump, reservoir or river from above, without touching the water.
- Range
- 0.3 to 12 m
- Accuracy
- ±2 mm, 1 mm resolution
- Beam
- 60 GHz, 8°
- Build
- IP68
- Power
- Own battery, around seven years at one report a day
- Not affected by dust, condensation or temperature
- Alarms on a threshold, a sudden change and its own tilt
- Keeps 2,000 readings and resends them after an outage
Fitted at Overhead tanks, sumps, reservoirs, rivers and sewers
Water quality
Whether water is fit to drink or to discharge, measured continuously or sampled at set intervals.
3 instruments
Water-quality probes
Digital probes for pH, conductivity and TDS, nitrate and residual chlorine, each read over RS-485 Modbus.
- pH
- 0–14, ±0.05
- Conductivity
- Up to 30,000 or 500,000 µS/cm, ±1% of full scale
- Nitrate
- 0.1 to 1,000 mg/L
- Residual chlorine
- 0–5, 10 or 20 mg/L, ±1% of full scale
- Build
- IP68, 10 m cable (to 100 m)
- Calibration is stored in the probe, so a probe calibrated in the lab is swapped on site
- Temperature measured for compensation
- The chlorine probe sits in a flow cell, with water flowing past it
Fitted at Treatment works, reservoirs, distribution points, plant water
Chlorine analyser
A sampling analyser for residual chlorine, where a reading is taken at a set interval rather than continuously.
- Alarms
- Low and high set points, 0–10 mg/L
- Link
- RS-485, up to 255 on one line
- Warns when reagent is low or old, or there is no sample
- Reports calibration errors and readings out of range
Fitted at Treatment works and service reservoirs
pH and redox converter
Turns a pH or redox (ORP) electrode into a reading the controller can take, with its calibration history.
- Range
- pH 0–14, or ORP ±1,500 mV
- Accuracy
- ±0.5% of range
- Build
- IP67, RS-485 Modbus
- Keeps its last five calibrations, with dates
- A calibration-due reminder, set from 0 to 365 days
Fitted at Treatment, effluent and process water
Air
The air at a city junction, a plant boundary or a mine, averaged for comparison with the standards.
1 instrument
Outdoor air-quality station
A station for up to eight air readings, for a city, a plant boundary, a mine or a tunnel.
- Particulates
- PM2.5 and PM10, 0–1,000 µg/m³
- Gases
- CO, O₃, NO₂, SO₂, CO₂ and total VOCs
- Weather
- Temperature, humidity, air pressure
- Reporting
- Every minute to every 24 hours
- Power
- Mains, or solar for at least 96 hours without sun
- Averages over 1 minute, 1 hour and 24 hours, to compare with the standards
- Mounts on a wall, roof, pole or the ground
- Links over RS-485, Wi-Fi, Ethernet or 4G
Fitted at City junctions, plant and mine boundaries, campuses
People
How many people use a space, counted from the ceiling without recording images.
1 instrument
Ceiling people counter
Counts people in and out of a doorway or a hall from the ceiling, without recording images.
- Accuracy
- Up to 99.8%
- Mounting
- Up to 3.5 m, or 6.5 m for high ceilings
- Lines
- Up to four counting lines, both directions
- Captures no images and works in the dark
- Leaves out staff wearing a tag, and people who turn back
- Queue regions with dwell time
Fitted at Cafeterias, entrances, halls and waiting areas
Networks
How the readings reach IoTyX: a gateway for battery-powered wireless sensors, and the controller itself.
2 instruments
Wireless sensor gateway
Gathers readings from battery-powered wireless sensors across a site and passes them to IoTyX.
- Sensors
- More than 2,000
- Reach
- About 2 km in a built-up area, up to 15 km in open line of sight
- Back link
- Ethernet, Wi-Fi or 4G, switching between them by itself
- Build
- IP65, −40 to 70 °C
- Desk, wall or pole mounting
- Speaks to building management systems over BACnet/IP
Fitted at Campuses, housing, plants and large sites
Ilonnati controller
The controller beside each machine, built on Ilonnati’s 4G/LTE board: it reads the instruments, drives the valve or pump, and reports to IoTyX.
- Link
- LTE Cat 1, two SIM slots
- Inputs
- RS-485 Modbus, CAN, analog inputs, encoder
- Drives
- A valve actuator or a pump
- Supply
- 5 to 60 V DC, 2 A
- Enclosure
- IP65/68, −40 to 85 °C
- A backup battery that reports a power failure
- Firmware updates over the air
- Designed by Ilonnati in Hyderabad
Fitted at Beside every valve, pump, tank and machine it runs
IS 10500:2012
Drinking-water limits
The limits in the Bureau of Indian Standards’ drinking water specification for the readings the probes take. IoTyX raises an alert when a reading crosses the limit set for it.
IS 10500:2012, the standard| Parameter | Acceptable limit |
|---|---|
| pH | 6.5 to 8.5 (no relaxation) |
| Total dissolved solids | 500 mg/L (2,000 mg/L permissible) |
| Residual free chlorine | At least 0.2 mg/L (1.0 mg/L permissible) |
| Nitrate | 45 mg/L (no relaxation) |
| Fluoride | 1.0 mg/L (1.5 mg/L permissible) |
| Arsenic | 0.01 mg/L (no relaxation) |