Pumps that follow the tank, supply on a timetable.

Pumps start and stop on the level of the tank they fill. Valves open at a set time and close when the meter has counted a set quantity. Neither needs anyone at the site.

In the field
Ilonnati controllers and sensors
On the screen
IoTyX: web, phone, control room
Illustration of a town water system: treatment works, an elevated reservoir, a pump house, the main with motorised valves, homes with meters, and an Ilonnati controller beside each valve and pump.

On a typical site

  1. Elevated reservoir
  2. Pump set
  3. Motorised valve
  4. Meter at each connection
  5. Ilonnati controller

In short

A pump house run by habit fills full tanks and runs pumps on empty sumps. Ilonnati puts a controller beside the pump and the outlet valve, with a level sensor in the tank. The pump starts at the tank’s low mark and stops at its high mark. For timed supply, a line is given slots, each with a time, a quantity and the days of the week it runs: at the time the valve opens, and when the meter has counted the quantity it closes. The slots are set from a phone and held at the controller. Overflow, late filling and a pump about to run dry raise alerts.

Who it is for

  • Water boards running pumping stations and reservoirs
  • Town and village water schemes
  • Housing communities with sumps and rooftop tanks
  • Plants that feed boiler, process or cooling tanks
  • Campuses with their own storage

Before and after

What changes

The same job, today and with Ilonnati.

  1. Today: An operator switches the pump by hand, often after the tank has run dry. With Ilonnati: The pump starts at the tank’s low mark and stops at its high mark, with no one at the switch.
  2. Today: A tank overflows because no one stopped the pump in time. With Ilonnati: Tank overflow raises an alert, and the overflow report shows when and where it happened.
  3. Today: A supply valve is opened by hand and closed by guesswork. With Ilonnati: The valve closes when the meter has counted the quantity set for that slot.
  4. Today: Supply times drift, and nobody records when filling really began. With Ilonnati: A tank whose filling starts late raises an alert, and deviations from the schedule are reported.
  5. Today: A pump runs on an empty sump, and the damage is found later. With Ilonnati: An alert warns when a pump is about to run with too little water to draw.

How it works

From the reading in the field to the action on the screen, and back.

  1. 01

    Set the slots

    On the phone, the operator opens a line, here a boiler-tank feed, and sets slots: 07:00 for 8,000 L, 16:00 for 2,000 L, 21:30 for 6,500 L, each on chosen days.

  2. 02

    Held at the controller

    The slots are sent to the controller beside the valve, and the app shows it connected and powered.

  3. 03

    The valve opens

    At 07:00 the valve opens. The status turns on, the meter counts up, and the flow curve rises on the phone.

  4. 04

    The quantity is reached

    At 8,000 litres the valve closes, the status returns to off, and the flow curve falls away.

  5. 05

    Pumps follow the level

    Elsewhere on the same platform, a sump pump starts when its overhead tank falls to the low mark and stops at the high mark.

  6. 06

    Exceptions are reported

    Late filling, overflow and schedule deviation appear as alerts and in the daily reports.

What is measured

Each reading reaches IoTyX through the Ilonnati controller beside the equipment.

ReadingWhat it tells you
Tank and reservoir levelWhen to start and stop the pump, before an overflow or a dry tank
Sump levelWhether the pump has water to draw, before it runs dry
Flow and running totalWhat each slot delivered, and when its set quantity is reached
Valve positionWhether the valve opened and closed on schedule, 0 to 100%
Pump stateWhether each pump is on, and its running hours
Pump house energyPower used at the pump house, against the water it moved

The rules and programmes behind it

Public programmes and rules that ask for this kind of measurement. Each links to the body that publishes it.

Industries where it applies

Each industry page sets out its equipment, its rules and the other use cases that run there.

Questions buyers ask

Not answered here?

Ask about your own network, plant or campus. An engineer will reply.

Contact us
01How is the pump controlled?

Through the same controller as the valves. Its relays switch the pump on or off, on the same command as a valve, and the controller confirms each change.

02Can different days have different slots?

Yes. Each slot has its own time, quantity and days of the week, and a line can hold several slots a day.

03What happens if a valve sticks?

The valve is given 60 seconds to reach its position and its motor is stopped at 90, so a stuck valve is not driven on. The controller reports the position it reached.

04Is it only for water supply?

No. The company’s own demonstration feeds a boiler tank in a plant on timed slots, and the same works for process and cooling tanks.